2015 Maxitrol Company. All Rights Reserved. DRAFT 09.18.2013 63 Dead End Lockup Pressure will be maintained within ANSICSA limits under no flow conditions. The amount of climb above set point is influenced by inlet pressure flow rate before no flow condition and piping arrangement. Dead end lockup pressure regulators must be properly sized for desired performance. Differential Pressure The difference between inlet pressure to the pressure regulator and outlet pressure from the pressure regulator. To obtain differential pressure subtract the desired outlet pressure from available inlet pressure. Line Pressure Regulator A pressure regulator intended for installation in a building gas distribution system between the building service regulator or LP-gas 2 psi service regulator and gas utilization equipment. Lockup Type Under no flow conditions outlet pressure will rise above adjusted pressure but will not rise to line pressure. Minimum Capacity Main Burner Only Minimum capacity of a pressure regulator designed to control the flow to the main burner only. Maximum Capacity Main Burner Only Maximum capacity of a pressure regulator at which the pressure regulator will control main burner pressure within acceptable limits. Maximum Capacity Main Burner and Pilot Maximum capacity of a pressure regulator at which the pressure regulator will control main burner and pilot line pressure within acceptable limits. Capacity Total load Btuh of all appliances combined. Maximum Individual Load Largest single appliance or burner served by the pressure regulator. Maximum Individual Load Capacity 1. The maximum capacity or flow at which a line pressure regulator will control lockup pressure within acceptable limits. 2. The maximum capacity or flow at which a pressure regulator will control pilot line pressure within acceptable limits. Non-Lockup Type Under static conditions when no gas is flowing outlet pressure will rise to line pressure. Overpressure Protection Device OPD Adevicewhichunderabnormalconditionswillacttoreduce restrict or shut off the supply of gas flowing into a system to prevent pressure in that system from exceeding 2 psi. Monitoring Regulator An overpressure protection device which functions as a second pressure regulator in series with the primary pressure regulator. Overpressure Relief Device An overpressure protection device which functions by discharging gas from the downstream system to a safe location. Overpressure Shut-Off DeviceAn overpressure protection device which functions by completely shutting off the flow of gas into the downstream system. Pressure Drop The natural loss of pressure that occurs in the pressure regulator or in any valve or pipe due to friction. This friction impedes fluid motion without regard to artificial losses deliberately created by diaphragm action. The equivalent flow rate for a loss in given pressure with the pressure regulator valve in a normally wide open position. Rated Inlet Pressure The highest inlet pressure for which the control is intended to be used. Vent Limiter A means that limits the flow of gas from the atmospheric chamber to the atmosphere in the event of a diaphragm rupture. This may be either a limiting orifice or a ball check vent limiting device. Limiting Orifice Type A vent limiter where the flow through the limiter is the same in both directions Zero Governors They require an external impulse signal such as top loading with pressure or generating vacuum in the downstream piping. DEFINITIONS