2015 Maxitrol Company. All Rights Reserved. DRAFT 09.18.2013 23 Model Pipe Size Inlet Pressure Outlet Pressure - inches w.c. kPa 2.0 0.5 4.0 1.0 6.0 1.5 9.0 2.25 12 3.0 16 4.0 20 5.0 24 6.0 28 7.0 210D 1 x 1 8.0 w.c. 2400 68.0 1900 53.8 1300 36.8 --- --- --- --- --- --- 0.5 psi 3400 96.3 3100 87.8 2700 76.5 2200 62.3 --- --- --- --- --- 0.75 psi 3500 99.1 4000 113 3800 108 3400 96.3 2900 82.1 2200 62.3 --- --- --- 1 psi 3500 99.1 4000 113 4500 127 4300 122 3900 110 3400 96.3 2700 76.5 1900 53.8 --- 1.5 psi 3500 99.1 4000 113 4500 127 4800 136 4800 136 5000 142 4600 130 4100 116 3600 102 2 psi 3500 99.1 4000 113 4500 127 4800 136 4800 136 5000 142 5000 142 5000 142 5000 142 3 psi 3500 99.1 4000 113 4500 127 4800 136 4800 136 5000 142 5000 142 5000 142 5000 142 5 psi 3500 99.1 4000 113 4500 127 4800 136 4800 136 5000 142 5000 142 5000 142 5000 142 7.5 psi 3500 99.1 4000 113 4500 127 4800 136 4800 136 5000 142 5000 142 5000 142 5000 142 10 psi 3500 99.1 4000 113 4500 127 4800 136 4800 136 5000 142 5000 142 5000 142 5000 142 NOTE CSA maximum capacities vary with spring range and pipe size. Please contact Maxitrol directly for CSA maximums. See pages 58-59 for Regulator Sizing Requirements and Examples. Capacities expressed in CFH m3 h 0.64 sp gr gas Capacities APPLIANCE REGULATORS C US UA.TR.012-13